Skip to product information
1 of 1

Eaton

Eaton MBS33NSB63BW | MBS Maintenance Bypass Switch, 3Ph/3Ph, 63A, 30-40kVA

Eaton MBS33NSB63BW | MBS Maintenance Bypass Switch, 3Ph/3Ph, 63A, 30-40kVA

Authorised Eaton Partner

SKU:MBS33NSB63BW

Request Quote
Sale Stock Status: Enquire
Shipping calculated at checkout.

Stock Status: Enquire

Description

The Eaton MBS maintenance bypass switch is a hardwired, wall-mounted external bypass for three-phase UPS systems rated 30-40kVA. It lets you isolate the UPS for service or replacement while the critical load stays powered from mains. This 3Ph/3Ph model is rated 63A with 16mm2 terminals and bottom cable entry, and uses a single input without a separate bypass input.

The make-before-break switching design keeps the load supplied when transferring between positions, and an interlock supports safe bypass operation. The black steel cabinet measures 368 x 214 x 490 mm and weighs 15 kg, and the unit is designed to the IEC 62040 UPS standard.

Features

- Make-before-break switching keeps the load supplied when transferring between positions
- Isolates the UPS for maintenance or replacement without interrupting the critical load
- Designed to the IEC 62040 UPS standard
- Interlock supports safe bypass operation
- Wall-mounted black steel cabinet with bottom cable entry

Warranty

• Standard UPS (with VRLA batteries): 2–3 year warranty
• Lithium-ion UPS (up to 3kVA): 5-year warranty
Extended Warranty Options:
Extended Eaton UPS warranties are available through IP Trading. Contact us to discuss a plan that suits your power protection needs.
https://www.eaton.com/us/en-us/catalog/services/ups-services/understanding-your-eaton-ups-warranty-.html

All technical data should be verified on the manufacturer data sheets.

View full details

specs-tabs

Collapsible content

Technical Specifications

FAQs

Replacement Battery Finder

Technical Specifications

- Device type: Wall-mounted maintenance bypass switch
- Phase configuration: 3Ph / 3Ph
- UPS power range: 30-40 kVA
- Rated current: 63 A
- Terminal size: 16 mm2
- Cable entry: Bottom
- Bypass input: Without separate bypass input (single input)
- Switch type: Make-before-break
- Interlock: Yes
- Dimensions (W x D x H): 368 x 214 x 490 mm
- Weight: 15 kg
- Enclosure: Black steel

FAQs

Q: What UPS size is this maintenance bypass switch suited to?
A: This model is intended for Eaton three-phase UPS systems in the 30-40kVA range and is rated at 63A.

Q: Does this model have a separate bypass input?
A: No. It is the version without a separate bypass input, so it operates from a single input.

Q: Does the load lose power when switching to bypass?
A: No. The switch uses make-before-break transfer, so the load stays supplied when moving between positions.

Q: What cable entry and terminal size does it use?
A: Cables enter from the bottom and the terminals accept 16mm2 conductors.

Q: How is the switch mounted?
A: It is a wall-mounted unit in a black steel cabinet measuring 368 x 214 x 490 mm and weighing 15 kg.

Q: Is it a plug-in unit?
A: No. It is a hardwired external maintenance bypass switch and must be wired in by a qualified electrician.

Replacement Battery Finder

Looking for an Eaton UPS replacement battery?

Use the official Eaton UPS Battery Finder tool to identify compatible battery replacement kits and genuine Eaton battery cartridges for your specific UPS model in Australia.

Find My Replacement Battery
Eaton Authorised Partner of the Year 2026 Australia Winner – IP Trading

Recognised by Eaton, two years running

We have been awarded as Eaton Authorised Partner of the Year 2026 - Australia, our second consecutive year of recognition.

As an authorised Eaton partner in Australia, we supply genuine Eaton UPS systems, rack PDUs and enterprise power protection solutions with expert product advice, fast turnaround, and reliable fulfilment.

Learn about our Eaton Partner Award
Black eaton server racks with blue led displays and network cables.

How to Choose the Right Eaton UPS

Use our Eaton UPS Selection Guide to compare UPS models, power capacity, runtime, and applications.

Learn how to correctly size a UPS for servers, network equipment, and critical IT infrastructure to ensure reliable backup power and protection from outages.

View the Eaton UPS Sizing Guide
  • Request for a Quote

    Looking for competitive pricing? Submit a request, and our team will provide a tailored quote that fits your needs.

  • Contact Us Directly

    Have a question or need immediate assistance? Call us for expert advice and real-time support.

    Call us Now  
  • Contact Us Directly

    Have a question or need immediate assistance? Call us for expert advice and real-time support.

    Contact us