Skip to product information
1 of 1

Moxa

Moxa MGate MB3270-G2-T | 2-Port Modbus Gateway, DB9, -40 to 75°C

Moxa MGate MB3270-G2-T | 2-Port Modbus Gateway, DB9, -40 to 75°C

Authorised Moxa Partner

SKU:MGate MB3270-G2-T

Stock Status: Enquire

Request Quote
Sale Stock Status: Enquire
Shipping calculated at checkout.

Description

The Moxa MGate MB3270-G2-T is a 2-port advanced Modbus gateway that converts between Modbus TCP, Modbus RTU and Modbus ASCII. This wide-temperature model has two software-selectable RS-232/422/485 serial ports on DB9 male connectors with no serial isolation, and is rated for -40 to 75°C operation, making it well suited to connecting serial Modbus devices to an Ethernet network in harsh industrial environments.

Two 10/100BaseT(X) RJ45 Ethernet ports support Ethernet cascading or dual subnet designs. The gateway supports transparent mode and agent (poll and cache) mode, handles up to 32 Modbus TCP clients and 32 servers, and offers dual redundant 12-48 V DC power inputs and a relay output. The metal IP30 housing mounts on a DIN rail or wall.

Features

- Converts between Modbus TCP, RTU, ASCII and proprietary/extended Modbus serial protocols
- Supports Modbus serial client to Modbus serial server communications
- Ethernet cascading or dual subnet for flexible network system design
- Built-in Modbus communication test tools that work without external software
- Modbus diagnostics and traffic monitoring for easier troubleshooting
- HTTPS/TLS secure configuration

Warranty

Moxa offers varying warranty periods depending on the product category:
• 5-Year Warranty: Applies to most industrial networking and connectivity products, including Ethernet switches, routers, wireless devices, serial converters, protocol gateways, and USB hubs.
• 3-Year Warranty: Covers x86-based industrial computers and panel PCs.
• 1-Year Warranty: Applies to external batteries, LCD panels, power adapters, antennas, and other select accessories.
Extended Warranty Options:
IP Trading offers tailored extended warranty solutions and support packages for Moxa products. Contact our team to explore options that align with your organization's needs.
https://www.moxa.com/en/support/repair-and-warranty/warranty-policy

All technical data should be verified on the manufacturer data sheets.

View full details

specs-tabs

Collapsible content

Technical Specifications

FAQs

Datasheet

Technical Specifications

- 2 x RS-232/422/485 serial ports (software-selectable), DB9 male
- 2 x 10/100BaseT(X) RJ45 Ethernet ports (Ethernet cascade or dual subnet)
- Serial baud rate 50 bps to 921.6 kbps; data bits 7/8; stop bits 1/2; parity None/Even/Odd/Space/Mark
- Serial flow control: RTS/CTS, DTR/DSR, RTS Toggle (RS-232 only)
- RS-485 automatic data direction control (ADDC); software-selectable 120 ohm terminator and 1k/150k ohm pull high/low resistors
- No serial isolation
- Modbus TCP Client/Server and Modbus RTU/ASCII Client/Server
- Transparent mode and Agent (poll and cache) mode
- 32 Modbus TCP clients and 32 servers; 128 commands; 150 tags / 2048 B tag memory
- Dual redundant 12-48 V DC power inputs; approx. 452 mA at 12 V DC
- Relay output: 1 A at 30 V DC (resistive load)
- Metal housing, IP30; DIN-rail or wall mounting
- Dimensions: 25 x 89 x 129 mm (without DIN-rail kit)
- Operating temperature: -40 to 75°C

FAQs

Q: What protocols does the MGate MB3270-G2-T convert between?
A: It converts between Modbus TCP, Modbus RTU and Modbus ASCII, and supports proprietary serial protocols in agent mode.

Q: Does this model provide serial isolation?
A: No. The MB3270-G2-T has no serial isolation. Isolation of 2 kV is only available on the 'I' models in this series.

Q: What operating temperature range does it support?
A: The -T wide temperature model operates from -40 to 75°C, suitable for harsh industrial cabinets and outdoor enclosures.

Q: What serial interfaces and connectors are fitted?
A: It has two software-selectable RS-232/422/485 serial ports on DB9 male connectors.

Q: Can the two Ethernet ports be used for redundancy or separate networks?
A: The two RJ45 ports support Ethernet cascading or a dual subnet configuration, which simplifies network design.

Q: How is the gateway powered and mounted?
A: It accepts dual redundant 12-48 V DC power inputs and mounts on a DIN rail or wall in a metal IP30 housing.

Datasheet

This product has a detailed PDF datasheet available. Open PDF datasheet in a new tab .

Your browser can’t display the embedded PDF. Click here to open it in a new tab.

Recently Viewed

  • Request for a Quote

    Looking for competitive pricing? Submit a request, and our team will provide a tailored quote that fits your needs.

  • Contact Us Directly

    Have a question or need immediate assistance? Call us for expert advice and real-time support.

    Call us Now  
  • Contact Us Directly

    Have a question or need immediate assistance? Call us for expert advice and real-time support.

    Contact us